Kingflex Kingflex

China Kingflex foam ruber tube pipe insulation Factories, Quotes

Kingflex foam ruber tube pipe insulation, Rubber as the main raw material ,no fiber ,non-formaldehyde, non-CFC and other ozone-depleting refrigerant ,can be directly exposed to the air, nor harm for human health. Standard product is black, It also efficiently reduces heat transfer for hot-water plumbing and liquid-heating and dual-temperature piping. It is ideal for applications in ductwork, dual temperature and low pressure steam line,process piping Air-conditioner, including hot gas piping. Nominal wall thicknesses of 1/4”, 3/8″, 1/2″, 3/4″,1″, 1-1/4”, 1-1/2″ and 2” (6, 9, 13, 19, 25 , 32, 40 and 50mm). Standard Length with 6ft (1.83m) or 6.2ft(2m).

Product Description

Rubber foam insulation tube is a uniquely formed closed cell flexible elastomeric insulation, used to insulate heating, ventilating, air-conditioning, refrigerating (HVAC/R). The insulation tube is also CFC/HCFC free, non-porous, fiber free, dust free and resistant to mold growth. The recommended temperature range for insulation is -50℃ to +110℃.
Key Performance Characteristics

Closed-cell Structure

Low Heating Conductivity

Low Water Absorption Rate

Good Fireproof and Soundproof

Good Aging Resistance Performance

Simple and Easy Installation

Technical Data Sheet
Technical Data
Property Unit Value Test Method
Temperature range °C (-50 - 110) GB/T 17794-1999
Density range Kg/m³ 45-65Kg/m³ ASTM D1667
Water vapor permeability Kg/(m.s.pa) ≤0.91×10 ﹣¹³ DIN 52 615 / BS 4370 Part 2 1973
μ - ≥10000 -
Thermal Conductivity W/(m.k) ≤0.030 (-20°C) ASTM C 518
≤0.032 (0°C)
≤0.036 (40°C)
Fire Rating - Class 0 & Class 1 BS 476 Part 6 part 7
Flame Spread and Smoke Developed Index - 25/50 ASTM E 84
Oxygen Index - ≥36 GB/T 2406, ISO4589
Water Absorption, %by Volume % 20% ASTM C 209
Dimension Stability - ≤5 ASTM C534
Fungi resistance - Good ASTM 21
Ozone resistance Good GB/T 7762-1987
Resistance to U.V. and weather Good ASTM G23
Product Gallery
Insulation Pipe
Insulation Performance
Closed Cell Structure
Fireproof Testing
Thermal Insulation Process
Technical Specifications
Insulation Details
Piping Application
Production Process
Warehouse Storage
Application Case
Product Properties
Final Packing
Frequently Asked Questions
What is the recommended temperature range for this insulation tube?
The recommended operating temperature range for our rubber foam insulation tube is -50℃ to +110℃, making it suitable for a wide variety of HVAC/R and heating applications.
Is this insulation material fire-resistant?
Yes, it achieves a Class 0 & Class 1 fire rating according to BS 476 Part 6 & Part 7 test standards. It also features a low Flame Spread and Smoke Developed Index of 25/50 under ASTM E 84.
Does this product contain CFCs or HCFCs?
No, our rubber foam insulation tube is entirely CFC/HCFC free. Additionally, it is fiber-free, dust-free, non-porous, and resistant to mold growth, ensuring high environmental and indoor air quality.
What makes the closed-cell structure beneficial?
The closed-cell structure provides exceptional resistance against water vapor permeability (μ ≥ 10000) and ensures low water absorption. This maintains low heating conductivity over time and prevents moisture buildup inside the insulation.
Is this material resistant to environmental factors like U.V. and ozone?
Yes, the technical data shows good resistance against ozone (per GB/T 7762-1987), good fungi resistance (per ASTM 21), and good resistance to U.V. and weather conditions (per ASTM G23).

Related Products