Kingflex
| Technical Data | |||
|---|---|---|---|
| Property | Unit | Value | Test Method |
| Temperature range | °C | (-50 - 110) | GB/T 17794-1999 |
| Density range | Kg/m³ | 45-65Kg/m³ | ASTM D1667 |
| Water vapor permeability | Kg/(m.s.pa) | ≤0.91×10⁻¹³ | DIN 52 615 / BS 4370 Part 2 1973 |
| μ | - | ≥10000 | - |
| Thermal Conductivity | W/(m.k) | ≤0.030 (-20°C) | ASTM C 518 |
| ≤0.032 (0°C) | |||
| ≤0.036 (40°C) | |||
| Fire Rating | - | Class 0 & Class 1 | BS 476 Part 6 part 7 |
| Flame Spread and Smoke Developed Index | - | 25/50 | ASTM E 84 |
| Oxygen Index | - | ≥36 | GB/T 2406, ISO4589 |
| Water Absorption, % by Volume | % | 20% | ASTM C 209 |
| Dimension Stability | - | ≤5 | ASTM C534 |
| Fungi resistance | - | Good | ASTM 21 |
| Ozone resistance | Good | GB/T 7762-1987 | |
| Resistance to U.V. and weather | Good | ASTM G23 | |
The material operates effectively within a temperature range of -50°C to 110°C, tested in compliance with the GB/T 17794-1999 standard.
It offers low thermal conductivity: ≤0.030 W/(m.k) at -20°C, ≤0.032 W/(m.k) at 0°C, and ≤0.036 W/(m.k) at 40°C, tested under ASTM C 518.
No. Thanks to its closed-cell structure and built-in vapor barrier design, it eliminates the necessity for installing an additional vapor retarder.
The insulation meets Class 0 & Class 1 fire rating requirements (BS 476 Part 6 & 7) and maintains a Flame Spread and Smoke Developed Index of 25/50 (ASTM E 84).
Yes. It features good resistance to ozone, UV rays, and general weathering, effectively retarding degradation caused by ultraviolet radiation over time.
Yes. The material is highly flexible and features dusted, relaxed inner diameters (IDs) designed for smooth handling and easy installation on site.